SHIHLIN S-P16 1NC 1NO CONTACTOR [230V/440V COIL]
රු6,250.00
The S‑P16 is a 3‑pole, 3‑phase magnetic contactor designed for controlling AC motors or general load circuits via a control coil. It is suitable for industrial and commercial electrical switching applications.
Add to Wishlist
Add to Wishlist
Description
Key Specifications
| Parameter | Value / Detail |
|---|---|
| Rated Operating Current (AC3) @ 380 V | 18 A |
| Rated Motor Capacity @ 380 V | 7.5 kW / 10 HP |
| Poles | 3‑pole (3P) |
| Contact Configuration | 1 NO + 1 NC auxiliary contact (standard) |
| Coil / Control Voltage Options | 220 V/ 440 V) |
Standards & Compliance
- IEC 60947‑4-1
- EN 60947‑4-1
- UL 508
- CSA C22.2
Rated Breaking Capacity (Example Loads)
| Supply Voltage | Capacity (kW / HP / A) |
|---|---|
| 240 V AC (3-phase) | 4.6 kW / 6 HP / 18 A |
| 380 V AC (3-phase) | 7.5 kW / 10 HP / 18 A |
Typical Applications
- Controlling 3‑phase motors such as pumps, compressors, and conveyors
- General power circuits and load switching in industrial or commercial electrical panels
- Integration into motor-starter assemblies when paired with thermal overload relays
Usage Notes & Recommendations
- Ensure coil voltage matches your control circuit.
- Pair with a thermal overload relay for motor protection; the contactor alone does not provide overload protection.
- Confirm motor working and starting current stays within the rated 18 A limit.
- Install in a clean, dry enclosure and follow standard wiring practices to maximize contactor lifespan.
Additional information
| Coil Voltage | 220 VAC, 440 VAC |
|---|





![SHIHLIN S-P125T 2NC+2NO MAGNETIC CONTACTOR [230V COIL]](https://generalpower.lk/wp-content/uploads/2025/12/OB-S-P125T-346x310.jpg)

Reviews
There are no reviews yet.