POTRIC ROTARY CHANGEOVER SWITCH
රු5,750.00 – රු8,500.00
1.Products Introduction
The LW26 sereies rotary switch mainly applies to 440V and below,AC 50Hz or 240V and below DC circuits.
For breaking and closing,change-over of circuits under unfrequenly manual operation.
And the typical application are: control switch of 3 phase motors, control switch gear,
control switch of instruments,and change-over switch of machinery and welding machine.
The series comply with the GB 14048.3,GB 14048.5 and IEC 60947-3,IEC 60947-5-1.
The LW26 series have 10 current ratings:10A,20A,25A,32A,40A,63A,125A,160A,250A and 315A.
They were designed for multiple functions,wide variety of applications.
The LW26-10,LW26-20,LW26-25,LW26-32F,LW26-40F and LW-60F have finger protection terminals.
LW26 series rotary switch are an excellent substitute for LW2,LW5,LW6,LW8,LW12,LW15,HZ5, HZ10,and HZ12.
The LW26 series rotary switch has two derivatives,LW26GS Pad-lock type and LW26S Key-lock type.
Both of them are applicable in circuits when an physical control is required.
We can equip protective box(IP65) for 20A to 250A.
Description
1.Products Introduction
The LW26 sereies rotary switch mainly applies to 440V and below,AC 50Hz or 240V and below DC circuits.
For breaking and closing,change-over of circuits under unfrequenly manual operation.
And the typical application are: control switch of 3 phase motors, control switch gear,
control switch of instruments,and change-over switch of machinery and welding machine.
The series comply with the GB 14048.3,GB 14048.5 and IEC 60947-3,IEC 60947-5-1.
The LW26 series have 10 current ratings:10A,20A,25A,32A,40A,63A,125A,160A,250A and 315A.
They were designed for multiple functions,wide variety of applications.
The LW26-10,LW26-20,LW26-25,LW26-32F,LW26-40F and LW-60F have finger protection terminals.
LW26 series rotary switch are an excellent substitute for LW2,LW5,LW6,LW8,LW12,LW15,HZ5, HZ10,and HZ12.
The LW26 series rotary switch has two derivatives,LW26GS Pad-lock type and LW26S Key-lock type.
Both of them are applicable in circuits when an physical control is required.
We can equip protective box(IP65) for 20A to 250A.
2.Working Conditions
a.Ambient temperature DO NOT exceed 40℃, and the average temperature,measured over a period of 24 hours,
DO NOT exceed 35℃.
b.Ambient temperature should not be below -25℃.
c.Should not be isstalled above 2000m above sea level.
d.The humidity should not exceed 50% when the ambient temperature is 40℃ and higher humidity is allowed for lower temperature.
3.Installation Conditions
a.A clean environment is required
b.Please follow our manual
4.Order Procedure
When placing an order please specify the contact diagram of the product you require.The LW26 series rotary switch have the similar contact diagram as the other rotary switches like LW2D,LW5D,LW6D,LW8D,LW12,LW15,HZ5D and HZ25D.Our factory have published<The General Contact Diagram for Cansen Rotary Switches >Which will help you to specify the contact diagram.
In addition,please specify the current rating, mounting plate,handle type,color and quantityas well.
Type
|
CA10-20
|
CA10-25
|
CA10-32
|
CA10-63
|
CA10-125
|
CA10-160
|
CA10-200
|
CA10-400
|
|
Rated Insulation Voltage Ui(V)
|
660
|
660
|
660
|
660
|
660
|
660
|
660
|
660
|
|
Conventional Heating Current Ith(A) Ac10≤40°
|
20
|
25
|
32
|
63
|
125
|
160
|
200
|
400
|
|
Rated Working Voltage Ue(V)
|
120 240 440
|
120 240 440
|
120 240 440
|
240 440
|
240 440
|
240 440
|
240 440
|
240 440
|
|
Rated Working Current Ie(A)
|
AC-21A AC-22A
|
20 20
|
25 25
|
25 32 32
|
63 63
|
100 100
|
150 150
|
180 180
|
360 360
|
AC-23A
|
15 15
|
22 22
|
22 30 30
|
57 57
|
90 90
|
135 135
|
150 150
|
360 360
|
|
AC-2
|
15 15
|
22 22
|
22 30 30
|
57 57
|
90 90
|
135 135
|
150 150
|
360 360
|
|
AC-3
|
11 11
|
15 15
|
15 22 22
|
36 36
|
75 75
|
95 95
|
110 110
|
140 140
|
|
AC-4
|
3.5 3.5
|
6.5 6.5
|
6.5 11 11
|
15 15
|
30 30
|
55 55
|
70 70
|
110 110
|
|
AC-15
|
5 4
|
8 5
|
5 14 6
|
– –
|
– –
|
– –
|
– –
|
– –
|
|
AC-13
|
5 1
|
9 1.5
|
25 11
|
– –
|
– –
|
– –
|
– –
|
– –
|
|
Rated Control Power(KW)
|
AC-23A
|
3.7/2.5 7.5/3.7
|
5.5/3 11/5.5
|
7.5/4 15/7.5
|
15/10 30/18.5
|
30/15 45/22
|
37/22 75/37
|
45/27 85/40
|
75/37 132/55
|
AC-2
|
4 7.5
|
5.5 11
|
7.5 15
|
18.5 30
|
30 45
|
37 55
|
45 60
|
55 95
|
|
AC-3
|
3/2.2 5.5/3
|
4/3 7.5/3.7
|
5.5/4 11/5.5
|
11/6 18.5/11
|
15/7.5 30/13
|
22/11 37/18.5
|
28/15 45/22
|
37/22 55/30
|
|
AC-4
|
0.55/0.75 1.5/1.5
|
1.5/1.1 3/2.2
|
3.7/1.5 5.5/3
|
5.5/2.4 7.5/4
|
6/3 12/5.5
|
10/4 15/7.5
|
12.5/6 22/9
|
15/7.5 25/11
|
|
Mechanical Life
|
60 x 104
|
||||||||
Electrical Life
|
AC-15 20 x 104 DC-13 6 x 104
|
Additional information
Weight | N/A |
---|---|
Dimensions | N/A |
POTRIC MTS | 32A 2POLE, 32A 4POLE, 63A 4POLE |
Reviews